The 2500P-ECC1 module supports the following communications protocols:
• CAMP Server
• CAMP Client
• Modbus Server
• Modbus Client
• Network Data Exchange
See CHAPTER 2 for information on these protocols.
Using a CTI-supplied configuration program, you can select the protocols to be used and
designate how they will operate. Configuration data is saved on a removable SD memory card,
located on the 2500P-ECC1 circuit board. If a module ever fails, a replacement can quickly be
placed in service by transferring the SD card from the failed unit to the new one.
Client requests to read data from the 2500 Series® controller are serviced from a data cache
maintained on the 2500P-ECC1 module. The frequency of cache updates is user configurable.
This data cache design allows protocols such as CAMP Server to provide rapid response to a high
volume of requests from SCADA workstations, HMI equipment, and operator panels while
providing a means to manage data quality.