Variant Description
Functionally the MTL4500 and MTL5500 range of modules are the same but differ in the following way:
– the MTL4500 modules are designed for backplane mounted applications
– the MTL5500 modules are designed for DIN-rail mounting.
In both models the hazardous area field-wiring connections (terminals 1.2. and optionally 4.5) are made through
the removable blue connectors, but the safe area and power connections for the MTL454xA/MTL454xAS
modules are made through the connector on the base, while the MTL554xA/MTL554xAS modules use the
removable grey connectors on the top and side of the module.
Note that the safe-area connection terminal numbers differ between the backplane and the DIN-rail
mounting models.
Note: To avoid repetition, further use of MTLx54xA and MTLx54xAS in this document can be understood to
include both DIN-rail and backplane models. Individual model numbers will be used only where there is a need
to distinguish between them.
All the module types described in this manual have the same connectivity for the field signals, supporting
4-wire process transmitters or currents sourced in the hazardous area. The connection of the repeated current
signals into the input measurement channels for the safety logic system follows the arrangement shown in the
following diagram. When the input channels of the Safety Instrumented System (SIS) are providing power for
the loop, the ‘S’ variants of the isolator modules are used to ‘sink’ the measuring current.
In the other cases the isolator modules ‘source’ the measuring current that flows into a load resistor inside the
input card of the Safety Instrumented System.