Ordering Information

The PXMP Meter system offers the flexibility to be used in a variety

of applications and can be customized, using the modular compo

nents, to fit most installations .  Table 1 lists the modular components

available for the PXMP Meter system

Metering Compatibility

Direct Mains Voltage Monitoring with the PXMP Meter is possible

up to a system maximum rating of:

• 480VL:G (corner grounded Delta)

• 347VL:N & 600VL:L maximum for Wye applications

• 480VL:G & L:L maximum on grounded Delta applications

Higher Voltage ratings or floating Delta applications will require the

use of interposing potential transformers to stay within the PXMP

maximum voltage ratings .

PXMP Load Current measurements are directly compatible with

current sensor (instrument transformers) outputs in three ranges of

secondary maximum outputs by using matching range PXMP Meter

Modules:

• 10 mA;

• 100 mA; or

• 333 mV .