MECHANICAL

Enclosures

An enclosure is required to house and protect the Megablock device coupler and the

F30 Ex ic adaptor for field operation. The type of enclosure must be chosen to suit

both the hazardous atmosphere likely to be encountered and the general conditions

appropriate to its environmental exposure. For installation in hazardous areas, the

enclosure must meet the requirements of a recognised method of protection

according to IEC 60079-0. clause 1.  In addition, the following conditions should

always be considered to ensure safe and reliable operation.

a) Prevent any form of pollution that could compromise the operation.

b) Provide an adequate level of mechanical protection. This can be achieved

by selecting a protected location, a suitable enclosure, or a combination of

both.

c) Ensure that all cable entries and connections are secure by making

provision for the careful routing and securing of all cables.

d)Provide adequate security against unauthorized interference.

e) Conform to the permitted ambient operating temperature range of  –40°C to +70°C.