Power supplies
For Ex ic spur applications, the F30 and associated Megablock must be supplied by
9192-FP power supply modules in simplex or redundant configuration. The 9192
FP module has the necessary voltage limiting and is designed to fit on one of the
backplanes from the 918x-x2 range of fieldbus power supply systems, all of which
are capable of providing n+1 redundancy for maximum availability.
The 918x family of redundant power supplies contains a range of solutions to suit
different host interfaces, consult Eaton for the model appropriate to the host and
install the chosen model in accordance with the instructions provided with it.