INSTALLATION
MOUNTING
MTL-Relcom Redundant Fieldbus Power Systems (FPS) are designed for
mounting on 35mm DIN rail. For maximum cooling, the DIN rail should
be mounted horizontally so that air can flow vertically between the
power modules.
INPUT POWER SUPPLY CONNECTIONS
For redundant operation, two separate DC power supplies should be
connected to each FPS. Four pairs of terminals are provided on each
FPS for this purpose; two pairs for each input power supply. The extra
pair of terminals for each input power supply are intended to be used
for connection to another FPS installed immediately adjacent to the first.
Prefabricated jumper assemblies are included with each FPS-I for this
purpose. When multiple Fieldbus Power Systems are wired together
using jumper assemblies, redundant connections should be made to the
two input power supplies using the terminal pairs located at each end of
the row of systems.