CERTIFICATION
MTL7000 Series barriers protect devices located in all normally
occurring explosive atmospheres, including air/flammable gas
mixtures, dusts and fibres. MTL7000 Series barriers are certified [EEx
ia] IIC (except MTL7129P+, certified IIB) BY BASEEFA to CENELEC
standards, by FM in the USA, CSA in Canada and also by other
authorities, providing worldwide certification. MTL7000 Series
barriers are designed to the same safety descriptions as MTL700
Series equivalents (in some cases slightly stricter) and can therefore be
used for the same applications.
HOW THEY WORK
All MTL7000 Series barriers are based on the same simple principle.
Each channel contains three stages of Zener or forward-connected
diodes and an ‘infallible’ terminating resistor. In the event of an
electrical fault in the safe area, the diodes limit the voltage that can
reach the hazardous area and the resistor limits the current: active
output-current limiting circuits are not used. An internal fuse protects
the diodes, and the three stages of voltage limitation ensure continued
safety if the first or second stage should fail. MTL7100 barriers have
an additional replaceable fuse which protects the internal fuse.
The MTL7000 Series includes seven key barrier types which cover the
majority of applications, simplifying barrier selection and the
maintenance of spares stocks.