Slave, Transmitter and Input addressing
The following discusses the allocation of addresses to the slaves on the Modbus
network – including the MTL838C – and the allocation of addresses for the
transmitters and inputs connected to each MTL838C.
Addressing MTL838C slaves
Modbus allows slave addresses in the range 1 to 247. JBUS allows slave
addresses in the range 1 to 255. This is the only difference between the two
protocols. Since the MTL838C can only have addresses in the range 1 to 31. it will
work equally well with either protocol.
The Modbus address for each MTL838C slave is set via the PC software. For
reasons of security, it is not possible to set the address of the slave via the
Modbus host.
The address for each RS485 port on the MTL838C may be set from 1 to 255. This
facility allows the MTL838C to be connected to the same master twice or to two
different masters independently. There is no restriction regarding simultaneous
communication on both ports. The unit will respond via the port on which it
received the query.