High Burden Tripping Types MVAJ 21. 23. 25. 26. and 29

These relays are suitable for use in high security circuit breaker tripping circuits.

particular they can be used in distributed tripping or control relay contact logic

where the initiating contact may be remote from the relay. The relays have a high

which is either cut-off at operation or economized to a low figure, either

or after a time delay.

The high burden provides immunity to capacitance discharge currents, which can result

the inception of an earth fault on battery wiring and immunity to the subsequent

current.

The high burden also permits the use of supervision relays such as type MVAX where

wiring is at risk and provides reliable operation of series elements such as repeat

type MCAA. For the latter purpose, type MVAJ relays can be provided with a time

economizing feature.

Control Relay Type MVAJ 34

This is a dual-rated electrical-reset relay, the main function of

which is to switch protection and autoreclosing equipment in and

out of service from a remote point via pilot wires. It complies with

NGC SPEC. NGTS2.19:1996.