High Burden Tripping Types MVAJ 21. 23. 25. 26. and 29
These relays are suitable for use in high security circuit breaker tripping circuits.
particular they can be used in distributed tripping or control relay contact logic
where the initiating contact may be remote from the relay. The relays have a high
which is either cut-off at operation or economized to a low figure, either
or after a time delay.
The high burden provides immunity to capacitance discharge currents, which can result
the inception of an earth fault on battery wiring and immunity to the subsequent
current.
The high burden also permits the use of supervision relays such as type MVAX where
wiring is at risk and provides reliable operation of series elements such as repeat
type MCAA. For the latter purpose, type MVAJ relays can be provided with a time
economizing feature.
Control Relay Type MVAJ 34
This is a dual-rated electrical-reset relay, the main function of
which is to switch protection and autoreclosing equipment in and
out of service from a remote point via pilot wires. It complies with
NGC SPEC. NGTS2.19:1996.