Multilin™ G60
Comprehensive Protection for Generators
The Multilin G60 generator protection system provides comprehensive protection for medium and
large generators, including large steam and combustion turbines, combined-cycle generators and
multicircuit hydro units.
The G60 includes advanced automation and communication capabilities, extensive I/O options,
and powerful fault recording features that can simplify postmortem disturbance analysis and help
minimize generator downtime.
100% Stator Ground 3rd Harmonic
100% stator ground fault protection is provided through a voltage differential feature that
responds to the unbalance of the third harmonic at the machine terminals and at the neutral
point. This method is insensitive to the absolute value of the third harmonic and is easily set
without the need for on-line measurements.
For generators with delta connected PTs, a third harmonic undervoltage element is also offered
for detecting a loss of the third harmonic voltage at the generator neutral.
Breaker Failure Protection
The breaker failure protection element monitors for timely operation of the connected breaker.
If a trip command is not successful in operating the breaker and clearing the fault, the breaker
failure element can be used to send trip signals to upstream breakers to clear the fault.