Description
Low Burden Tripping Relay Types MVAJ 11. 13. 14
These relays are suitable for applications where immunity to
capacitance discharge and high minimum operation currents are
not required.
Control Relay Type MVAJ 34
This is a dual-rated electrical-reset relay, the main function of
which is to switch protection and autoreclosing equipment in and
out of service from a remote point via pilot wires. It complies with
NGC SPEC. NGTS2.19:1996.
High Burden Tripping Relay Types MVAJ 21. 23. 25. 26. 27
Versions have one or two contact stacks depending on the number
of output contacts required.
Type MVAJ 21 High Burden Self-resetting Relay
This uses a contact on the main contact stack to energize a
separate, rear-mounted economizing element. After operation,
this reduces the burden by switching in resistance in series with
the main element and switching out shunt resistance.
Figure 2 shows a typical circuit diagram for self-resetting relays of
this type with high speed economy. When the main attracted
armature unit RL1 is energized by the protection contact PR, a
contact RL1-a energizes auxiliary element RL2. When contacts
RL2-a and RL2-b open, resistor R4 is put in series with RL1 while
the circuit to resistor R2 is broken.