Product Description

The X-HART 32 01 module is a 32-channel communication module, intended for use in the

programmable electronic system (PES) HIMax.

The module is inserted into any of the base plate slots with the exception of the slots reserved

for system bus modules. For more information, refer to the System Manual (HI 801 001 E).

The connector boards can be used to allow the module to be combined with analog input or

output modules.

The HART protocol is operated on the module. HART is used for digital field communications

during which the HART signal is superimposed onto the (4…20 mA) analog current signal.

The HART signal is used to transfer the measuring and device data to sensors or actuators. The

X-HART modules transfer the HART data to the assigned X-COM module within the HIMax

system. The X-COM module transfers the HART data via the HART over IP protocol to the host

(asset management system or HART OPC server).

The X-COM module and the assigned X-HART modules form a I/O system as referred to in the

HART specification.

The module has been certified by the TÜV for safety-related applications up to SIL 3

(IEC 61508. IEC 61511 and IEC 62061) as well as Cat. 4 and PL e (EN ISO 13849-1).

Refer to the HIMax Safety Manual (HI 801 003 E) for more information on the standards used to

test and certify the module and the HIMax system.