Safety Function
The module ensures its safety function using one extra safety switch for each channel pair
that is opened if a failure occurs.
The safety function is performed in accordance with SIL 3.
Reaction in the Event of a Fault
If the safety-related processor system of the module detects a module fault during
operation, the module adopts the safe state after a maximum of 16 ms and all the outputs
are de-energized in accordance with the ‘de-energize to trip principle’. If a channel fault
occurs, both channels of the affected channel group are switched off.
The module activates the Error LED on the front plate.
Scope of Delivery
The module must be installed on a suitable connector board to be able to operate. If a FTA
is used, a system cable is required to connect the connector board to the FTA. Connector
boards, system cables and FTAs are not included within the scope of delivery.
The connector boards are described in Chapter 3.6. the system cables are described in
Chapter 3.7. The FTAs are described in own manuals.