Product Description
The X-DI 32 05 digital input module is intended for use in the programmable electronic
system (PES) HIMax.
The module can be inserted in any of the base plate slots with the exception of the slots
reserved for system bus modules. For more information, refer to the System Manual
(HI 801 001 E).
The module is used to evaluate up to 32 safety proximity switches (e.g., P+F), proximity
switches in accordance with EN 60947-5-6 (NAMUR) or wired contacts.
The module is suitable for sequence of events recording (SOE). Events are recorded within
a module cycle of 2 ms, refer to Chapter 4.2.2 for more information.
The module has been certified by the TÜV for safety-related applications up to SIL 3
(IEC 61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1).
Refer to the HIMax Safety Manual (HI 801 003 E) for more information on the standards
used to test and certify the module and the HIMax system.