Safety Function
The module evaluates the input signals of proximity switches and contact makers and
monitors the proximity switch / contact maker circuit for open-circuits and short-circuits.
The safety function is performed in accordance with SIL 3.
Reaction in the Event of a Fault
If a fault occurs, the module adopts the safe state and the assigned input variables transmit
the initial value (default value = 0) to the user program.
The initial values must be set to 0 to ensure that the input variables transmit the value 0 to
the user program if a fault occurs. If the raw value is evaluated instead of the process
value, the user must program the monitoring function and the value in the event of faults
from within the user program.
The module activates the Error LED on the front plate.