Reaction in the Event of a Fault

If the safety-related processor system of the module detects a module fault during operation, the

module adopts the safe state:

 0 is output for the Rotation Speed parameter and 0 (0 = unequal) for the Rotation Sense

parameter.

 All the assigned input variables transmit the initial value to the user program. The initial

values must be set to 0 to ensure that the input variables transmit the value 0 to the user

program if a fault occurs.

 All the outputs are de-energized in accordance with the de-energize to trip principle.