The UCN uses redundant coaxial cables and can support up to 32
redundant devices. The UCN supports peer-to-peer communication
between devices on this network. This feature enables sharing
information among HPMs, APMs, PMs, Safety Managers, and Logic
Managers on the network, thus offering tremendous power and
flexibility in implementing advanced, coordinated control strategies.
Network Interface Module The Network Interface Module (NIM)
provides the link between the Local Control Network and the
Universal Control Network.
Accordingly, it makes the transition from the transmission technique
and protocol of the Local Control Network to the transmission
technique and protocol of the Universal Control Network. The NIM
provides LCN module access to data from UCN-resident devices.
It supports program and database loads to the Advanced Process
Manager and forwards alarms and messages from the network
devices to the LCN. The NIM is also available in a redundant
configuration to provide automatic, continued operation in the event
of a primary failure.
LCN time and UCN time are synchronized by the NIM. The NIM
broadcasts LCN time over the UCN. The APM (as well as the HPM)
uses it for a number of time driven functions, such as sequence
of events reporting.