The KONGSBERG DZ-110/U Transmitter Barrier Unit is designed to
safely provide signal interface and pow er supply to Kongsberg
instrumentation located in hazardous area. The unit connects
intrinsically safe 4-20 mA transmitters.
Principle of operation
The Transmitter Barrier is installed in safe area, designed to
limit the amount of energy that could appear in an electric circuit
that connects to instrumentation located in hazardous area.
The DZ-110/U is a single channel shunt diode safety barrier,
intended for energising a 2-wire, 4-20 mA signal transmitter
installed in hazardous area. A “current mirror” amplifier re
peats the transmitter current into an equal magnitude safe
side current. To prevent leakage through the zener diodes, the
voltage applied to the barrier section is regulated and limited
to a suitable level. Active current limiting is also incorporated to
prevent fuse blow-out during accidental shorting of the transmit
ter circuit.