The AN-X-AMX Gateway lets you capture, store and analyze network data

on a Reliance AutoMax DCS or remote I/O network. The AN-X-AMX

gateway can be used to examine the behavior of all drops, verify network

data and timing, locate network errors and troubleshoot problems with the

network and with the process.

The AN-X-AMX gateway does not occupy a drop on the network or affect

existing network traffic in any way. The AN-X-AMX gateway captures and

stores ALL network frames, with timestamps to microsecond precision and

uses post-capture filtering to select frames of interest for further analysis.

This approach ensures that everything leading up to an event of interest is

preserved.

The alternative approach, pre-filtering and saving only certain messages,

might cause you to lose key information. At the end of each minute, a new

file is created and the file older than the keep time is deleted.

Typical capture file size is 2.5 megabytes/minute, 150 megabytes/hour,

3.6 gigabytes/day. The AN-X-AMX gateway is field upgradeable.

The operating system and firmware can be upgraded over Ethernet.