Features
♦ Meter Runs: The module can calculate up to 12 meter runs simultaneously with a maximum of 16 streams on
a single meter run (64 streams maximum per module shared among all 12 meter runs).
This flexibility provides a cost-effective, highly scalable solution for all your measurement applications.
♦ Modbus® Capabilities: Remote configuration and diagnostics via Ethernet (Modbus TCP/IP) or Serial (Modbus)
interfaces. Flexible serial port configurations allow for either two Modbus slave ports or one Modbus slave and
one Modbus Master port. All data, including configuration, calculated results, and historical archives, are available
using either the Modbus TCP/IP server or Modbus slave serial ports.
♦ Customized Modbus Data Mapping: Remapping to a virtual slave enables data concentration, reducing bandwidth
load on the communication system.
♦ Auditability: Our configuration software provides the ability to download and view archives and events. Audit Scan captures
process inputs and calculated results as “snapshots”, allowing verification of calculations. The Log files record significant events
and alarms. Hourly and daily archives are configurable historical records of user-selected data. The data can be viewed online,
printed, or saved to a file in .txt or .csv format. Archive data can be exported to Flow-Cal .cfx format. Meter calibration and
verification are stored on the module.
♦ Meter Proving: Allows for meter proving with 3 configurable prover types.
♦ Security: Password protection schemes are available to control user access and log meter calibration and verification activities.
A built-in web server allows for remote network diagnostics and monitoring.
Leave a comment