Functional Specifications
ASCII Communication ports 1 & 2 (PRT1. PRT2)
Both ports are capable of transmitting and/or receiving ASCII character strings.
Each port is individually configurable:
o Termination types
o Stream mode
o Termination character(s)
o Message timeout
o Intercharacter timeout
o Packet size limit
o Baud rate: 110 to 115.2K baud
o Parity: none, even, odd
o Stop bits: 1 or 2
o Data bits: 5 to 8
o RTS on/off timing: 0 to 65535 milliseconds
o Minimum response delay: 0 to 65535 milliseconds
Handshaking (optional)
o Hardware: RTS/CTS, DTR/DSR
o Software: XON/XOFF
ASCII character strings up to 4096 characters in length supported
Full hardware handshaking control provides radio, modem and multi-drop support
User-definable module memory usage, supporting the storage and transfer of
up to 4000 registers to/from the control processor
Module error and status conditions returned to processor for diagnostic purposes
o Module status
o Port error status word (bitmapped)
o Port receive state
o Port receive character count
o Port receive block count
o Port transmit state
o Port transmit character count
o Port transmit block count
All data related to the module is contained in a single controller tag with defined
objects to simplify monitoring and interfacing with the module
Module communication data is transferred to the module via a predefined user
data type in the processor