APPLICATION OVERVIEW
The easYview comes prepared with two basic application modes: a remoteHMI mode and a miniSCADA
mode.
In the remoteHMI mode, the easYview connects to one or more devices via VNC connection and
receives
the remote HMI screens of the connected easYgen-XT or LS-6XT devices. Depending upon the easYview
screen size (7’, 10’ or 15’), 1. 2 or 4 different remote HMI screens can be shown simultaneously.
This mode is suitable for detailed connection to a single controller and helps troubleshoot,
commission, parametrize, Alarm/event log etc.
In the miniSCADA mode, the easYview connects to multiple easYgen-XT or LS-6XT devices via Modbus
TCP connection and offers a plant level visualization. This mode is designed to keep operators informed
during regular operation and maintenance to visualize most frequent / favorite values often from system
perspective without going into details. The miniSCADA mode also has a built-in remoteHMI capability.
Off-the-shelf easYview comes prepared with 3 easYgen-3000XT controllers in island or utility parallel
operation.
Tunables are available for customizations such as, deleting an easYgen, changing color of live bus bar,
changing utility source data etc. However, for any major customization such as adding an easYgen-XT,
LS-6XT or 3rd party device, adjusting single line diagram, etc, an atvise® Builder tool is required.