APPLICATION OVERVIEW

The easYview comes prepared with two basic application modes: a remoteHMI mode and a miniSCADA

mode.

 In the remoteHMI mode, the easYview connects to one or more devices via VNC connection and

receives

the remote HMI screens of the connected easYgen-XT or LS-6XT devices. Depending upon the easYview

screen size (7’, 10’ or 15’), 1. 2 or 4 different remote HMI screens can be shown simultaneously.

This mode is suitable for detailed connection to a single controller and helps troubleshoot,

commission, parametrize, Alarm/event log etc.

 In the miniSCADA mode, the easYview connects to multiple easYgen-XT or LS-6XT devices via Modbus

TCP connection and offers a plant level visualization. This mode is designed to keep operators informed

during regular operation and maintenance to visualize most frequent / favorite values often from system

perspective without going into details. The miniSCADA mode also has a built-in remoteHMI capability.

Off-the-shelf easYview comes prepared with 3 easYgen-3000XT controllers in island or utility parallel

operation.

Tunables are available for customizations such as, deleting an easYgen, changing color of live bus bar,

changing utility source data etc. However, for any major customization such as adding an easYgen-XT,

LS-6XT or 3rd party device, adjusting single line diagram, etc, an atvise® Builder tool is required.