Important Considerations:

Communicating with legacy DSLC-2 (and MSLC-2)

Woodward will provide update files for legacy DSLC-2 and MSLC-2 devices in the field if

there is to run a mix of both DSLC-2/MSLC-2 generations.

The legacy device will then send their UDP messages in a way that DSLC-2XT/MSLC-2XT can evaluate.

It is mandatory to load this update file into the legacy devices for the system to run smoothly.

2. Using your existing settings file (*. WSET) from legacy DSLC-2 (and MSLC-2)

Woodward will provide a conversion rule for ToolKit to make the configuration transfer as smooth as possible.

Some minor parameters will be shown in a log file, to be evaluated manually.

3. The AC measurement of the DSLC-2XT (and MSLC-2XT)

The measurement hardware and software are different in comparison to the legacy devices.

This is mainly due to higher accuracy, more flexible measurement range and fast response characteristics.

The earthing of the DSLC-2XT/MSLC-2XT devices has become more important due to higher impedance of the measurement circuits.

4.ToolKit

To give you a seamless transition experience, the ToolKit layout (*. WTOOL file) is designed like the original devices.

There are few less parameters due to new AC measurement and communication interfaces.

5.Documentation server

Product literature (manuals, config. files, software etc.) is hosted on a documentation server

that is easily accessible by a QR code printed on the housing.

Two additional QR stickers are delivered with the controllers to help you paste them at a location convenient to you.

Subsequently, product CD is removed from scope of delivery.