Shutdown/Reset Discrete Input
When the shutdown contact is opened, the driver goes into a shutdown mode
and the valves are commanded to and held at minimum position. When the
shutdown contact is closed, the driver returns to ‘run’ mode and it resets all driver
faults.
Discrete Output for Driver Status Indication
The discrete output contact is normally on/closed (customer-supplied power
applied to load such as a trip-string relay) under normal driver operation, and
turns off/opens to indicate any detected shutdown condition within the driver.
Both alarm and shutdown indications are latching, which means a reset
command is required to clear the fault. The Service Tool program can be used to
interrogate the cause of the alarm or shutdown. The CAN communications can
also be used to determine alarm and shutdown causes.
The Swift Gas Metering System will continue to operate with an alarm condition
(for example, failure of the primary demand signal). However, the unit will cease
to operate on a shutdown condition (for example, failure of position demand input
signal).
Leave a comment
Your email address will not be published. Required fields are marked *