• True R.M.S. 3-phase voltage measuring for both Source 1 and Source 2
• True R.M.S. 3-phase load current/power
• Software configurable for wide range of ATS applications:
• Utility-to-Generator: Utility is preferred with a generator as emergency source
• Generator-to-Generator: One genset is preferred with a second genset as backup
• Utility-to-Utility: Utility is preferred with second utility as the emergency source
• Incorporates several monitoring features for a secure transfer: Source, Load, Switch, Battery, In-phase,
and parallel time monitor
• Intelligent limit switch feedback monitoring to ensure plausibility before initiating a transfer
• Fully configurable transfer command pulse configuration
• Inhibit transfer to S1. S2. both or start emergency source but initiate no transfer
• Elevator pre-signal with timer before carrying out a transfer
• Motor load disconnect signal with timer and possibility to daisy chain multiple MLDs for load
sequencing
• Source priority selection configurable via LogicsManager
• Load test and engine test to initiate routine health check of the emergency source
• In-phase monitoring ensures a transfer occurs within a phase angle difference of 70 or less
• Extended parallel time enables soft loading applications