SPECIFICATIONS

Power supply ………………………………………………….12/24 VDC (8 to 35 VDC)

Intrinsic consumption …………………………..  max. 6 W (standby max. 5 W)

Ambient temperature (operation) ……………….. -25 to 70 °C / -13 to 158 °F

Ambient temperature (storage) …………………. -25 to 70 °C / -13 to 158 °F

Ambient humidity…………………………………………….. 93%, non-condensing

Voltage …………………………………………………………………………………….. /

Rated (Vrated) …………………………………… 277/480 VAC

Max. value (Vmax) …………………………………… 358/620 VAC

Max. value (Vmax) according to UL …………… 173/300 VAC

Accuracy ……………………………………………………………………………. Class 1

Linear measuring range ……………………………………………………….. 1×Vrated

Measuring frequency …………………………………….. 50/60 Hz (40 to 85 Hz)

High Impedance Input; Resistance per path …………………………… 4.0 M

Max. power consumption per path ……………………………………….. < 0.2 VA

Current (Isolated)    Rated (Irated)…………………………………………….5A

Linear measuring range ……………………………………………… Igen = 2.0×Irated

Imains/ground = 1.5×Irated

Rated short-time overcurrent (1 s) ………………………………………… 10×Irated

Accuracy …………………………………………………………………………… Class 1

Discrete inputs group A [DI 1-7] ……………………………………. non isolated

Low level threshold ………………………………………………. Approx.… 1.3 VDC

High level threshold……………………………………………………………… 1.7 VDC

Max. input voltage ………………………………………………………………… 60 VDC

Min. input voltage …………………………………………………………………… 0 VDC

Discrete inputs group B [DI 8-12] ………………………………….. non isolated

Low level threshold ………………………………………………. Approx.… 1.3 VDC

High level threshold……………………………………………………………… 1.7 VDC

Max. input voltage ………………………………………………………………… 24 VDC

Min. input voltage …………………………………………………………………… 0 VDC

Display …………………………………………………………………………………………..

…………………………………………………… 480 × 272 TFT LCD with backlight

……. Wear resistant and scratch resistant LCD due to hard acrylic screen

Discrete outputs group A [R 2-4] ……………………………………………. isolated

……………………………………………… Rated 7 ADC, 24 VDC running standalone

………… Rated 3 ADC, 24 VDC when running in parallel with other two relays

………………………………………..3 ADC, 24 VDC resistive GP (according to UL)

Discrete output [R 5] ……………………………………………………………… isolated

………………………….. Rated 7 AAC, 250 VAC voltage free output, resistive GP

Discrete outputs group B [R 6-7] ……………………………………………. isolated

……………………………………………. Rated 10 ADC, 24 VDC running standalone

………….. Rated 5 ADC, 24 VDC when running in parallel with the other relay

……………………………………………. 2 ADC, 24 VDC inductive (according to UL)

Discrete output group C [R 8-9] ……………………………………………… isolated

………………………….. Rated 7 AAC, 250 VAC voltage free output, resistive GP

Interfaces …………………………………………………………………………………………..

USB service port ………………………………………………………………………………..

Max. allowed cable length ………………………………………………………….. 1.5 m

RS-485 interface ……………………………………………………………………. isolated

Insulation voltage …………………………………………………………………… 500 VAC

Max. allowed cable length ……………………………………………………….. 1000 m

CAN bus interface ………………………………………………………………….. isolated

Insulation voltage …………………………………………………………………… 500 VAC

Internal line termination ………………………………………………………… 120 Ohm

Housing Front panel flush mounting ……………………………….. Plastic housing

Dimensions  WxHxD …………………………………… 237 × 172 × 45 mm

Front cutout  WxH ………………………………………… 214.5 × 160.5 mm

Connection …………………………………………….. screw/plug terminals 2.5 mm²

Front ………………………………………………………………………. insulating surface

Sealing  Front ……………………………. IP65 (with screw fastening)

Back ……………………………………………………………. IP20

Weight ………………………………………………………………………. approx. 0.850 g

Disturbance test (CE) ………… tested according to applicable IEC standards

Approvals  ………………………. CE, UL recognized UL1008. File No: E527936