LogicsManagerTM – Woodward’s LogicsManager enables to change the operation sequences and adapt them

to specific needs. The LogicsManager accomplishes this by monitoring a range of measuring values and inter

nal states, which are combined logically with Boolean operators and programmable timers. This enables to

create and/or modify control and relay functions.

FlexInTM – The analog inputs are configurable to operate with VDO, resistive, and/or 0 to 20 mA senders.

Flexible Outputs – Speed and voltage bias outputs are configurable to function with all speed governors and

voltage regulators. The outputs can also be used as freely scalable outputs (e.g. for driving external meters).

FlexCANTM – Advanced network interfaces ensure unsurpassed control performance – from engine control up

to total plant operation. The easYgen-3000 Series is capable of working with all common industrial interfaces,

including CAN, RS-232. and RS-485. The multiple communication protocols permit the easYgen-3000 Series to

communicate with a vast majority of engine control units (ECUs), external I/O boards, PLCs, and modems.

CANopen, J1939. Modbus RTU, and Modem protocols are supported.

DynamicsLCDTM – The adaptive and interactive 5.7″, 320×240 pixel color graphical LC display with soft keys

and a clear menu structure ensures intuitive user operation and navigation.