FEATURES
• Enables several power generation topologies. Some frequently used are:
• only with easYgen-3500XT: 32 gensets, one generator group breaker and one mains circuit breaker
• with easYgen-3500XT and LS-5: 32 gensets and 16 breakers (Tie/GGB/MCB) or 16 gensets and 32
breakers on CAN bus
• with easYgen-3500XT and LS-6XT: 32 gensets and 32 breakers (Tie/GGB/MCB) on single or redundant
Modbus/TCP
• with easYgen-3500XT and GC-3000XT: 496 gensets, one generator group breaker and one mains circuit breaker
• with easYgen-3500XT, LS-6XT and GC-3000XT: The control topology is cascaded in three layers. Layer
1 consists of easYgen (and also LS-6XT), Layer-2 group controls and Layer-3 LS-6XT. At Layer-1 total
496 gensets (16 x 31), at Layer-2 16 Group controllers and at Layer-3 64 LS-6XT on up to 128 segments
are supported. Communication between Layer-1 and Layer-2 controls is CAN, Ethernet A or hot redun
dant CAN/Ethernet A and between Layer-2 and Layer-3 controls is Ethernet B, Ethernet C or hot redun dant Eth B/Eth C.