SPECIFICATIONS

Power supply ………………………………………………….12/24 VDC (8 to 40 VDC)

Intrinsic consumption ……………………………….  max. 22 W (LT: max.32 W)

Ambient temperature (operation) …………… -20 to 70 °C (LT: -40 to 70 °C)

Ambient temperature (storage) …………………. -30 to 80 °C / -22 to 176 °F

Ambient humidity…………………………………………….. 95%, non-condensing

Voltage (software configurable) …………………………………………….. ( /)

100 VAC  Rated (Vrated) …………………………………….. 69/120 VAC

Max. value (Vmax) …………………………………….. 86/150 VAC

and 400 /600 VAC  Rated (Vrated)* …………………………………… 400/690 VAC

Max. value (Vmax) …………………………………… 520/897 VAC

Rated surge volt. (Vsurge) ……………………………………………. 6.0 kV

Accuracy …………………………………………………………………………. Class 0.5

Measurable alternator windings . 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w

Setting range ………………. primary …………………………… 50 to 650.000 VAC

Linear measuring range …………………………………………………… 1.25×Vrated

Measuring frequency …………………………………….. 50/60 Hz (30 to 85 Hz)

High Impedance Input; Resistance per path …………………………… 2.5 M

Max. power consumption per path ………………………………………. < 0.15 W

Current (Isolated, software configurable)     Rated (Irated) ……… 1A or 5A

Linear measuring range ……………………………………………… Igen = 3.0×Irated

Imains/ground = 1.5×Irated

Setting range ……………………………………………………………… 1 to 32.000 A

Burden ……………………………………………………………………………. < 0.10 VA

Rated short-time overcurrent (1 s) ……………………[1] 50×Irated, [5] 10×Irated

Accuracy ………………………………………………………………………… Class 0.5

Power ……………………………………………………………………………………………

Setting range ……………………………………………….. 0.5 to 99.999.9 kW/kvar

Accuracy …………………………………………………………………………. Class 1.0

Discrete inputs …………………………………………………………………… isolated

Input range ……………………………………………………12/24 VDC (8 to 40 VDC)

Input resistance …………………………………………………… approx. 20 kOhms

Transistor outputs (P2 only) ………………………………………………… isolated

Rated switching voltage ………………………………………………… max. 24 VDC

Maximum switching voltage …………………………………………………… 40 VDC

Maximum switching current ……………………………………………. 300 mA DC

Isolation Test voltage (<1s) ………………………………………………….. 500 VAC

Isolation voltage (continuously) …………………………………………. 100 VAC/DC

Relay outputs ……………………………………………………………………… isolated

Contact material ………………………………………………………………….. AgCdO

Load (GP) …………………………………………………………… 2.00 AAC@250 VAC

2.00 ADC@24 VDC / 0.36 ADC@125 VDC / 0.18 ADC@250 VDC

Analog inputs (isolated) …………………………………………………freely scalable

Type 1 ………………………………………. 0 to 1 V / 0 to 2000 Ohms / 0 to 20 mA

Resolution ………………………………………………………………………………. 16 Bit

Maximum permissible voltage against genset Ground ……………………… 9 V

Maximum permissible voltage between genset Ground & PE ……….. 100 V

Type 2 (P2 only)…………………………………………………. 0 to 10 V / 0 to 20 mA

Resolution …………………………………………………………………………….. 14 Bit

Maximum permissible voltage against PE (Ground) …………………… 100 V

Maximum differential voltage to other DC Analog Inputs ………………. 15 V

Type 3 (P2 only)…………………………………. 0 to 250 Ohms / 0 to 2500 Ohms

Resolution …………………………………………………………………………….. 14 Bit

Maximum permissible voltage against PE (Ground) …………………… 100 V

Maximum differential voltage to other DC Analog Inputs ………………. 10 V

Analog outputs (isolated) ………………………………………………freely scalable

Type 1 ………………………………………………………….. ± 10 V / ± 20 mA / PWM

Basic insulation voltage (continuously, AVRout) ……………………….. 500 VAC

Reinforced insulation voltage (continuously, AVRout) ……………….. 300 VAC

Insulation voltage (continuously, Govout) ………………………………… 100 VAC

Resolution …………………………………………………………………………….. 12 Bit

Output ± 10 V (scalable) ……………………………………….. internal resistance

Output ± 20 mA (scalable) ………………………….. maximum load 500 Ohms

Type 2 (P2 only)……………………………………………………………… 0/4 to 20 mA

Insulation voltage (continuously) …………………………………………… 100 VAC

Insulation voltage (test; >2 s) ………………………………………………. 1700 VAC

Resolution …………………………………………………………………………….. 12 Bit

Output ……………………………………………………… maximum load 500 Ohms

Housing Front panel flush mounting ……………………………….. Plastic housing

Dimensions  WxHxD …………………………………… 282 × 216 × 96 mm

Front cutout  WxH ……………………………. 249 [+1.1] × 183 [+1.0] mm

Connection …………………………………………….. screw/plug terminals 2.5 mm²

Front ………………………………………………………………………. insulating surface

Sealing  Front ……………………………. IP66 (with screw fastening)

Front ……………………………. IP54 (with clamp fastening)

Back ……………………………………………………………. IP20

Weight ………………………………………………………………………. approx. 1.850 g

Housing Back panel mounting …………. Powder Coated Sheet metal housing

Dimensions  WxHxD  P1: …………………………….. 250 × 228 × 50 mm

P2: …………………………….. 250 × 228 × 84 mm

Connection …………………………………………….. screw/plug terminals 2.5 mm²

Protection system ……………………………………………………………………… IP 20

Weight ………………………………………………………………………. approx. 1.750 g

Disturbance test (CE) ………… tested according to applicable IEC standards

Listings  ……………………………… CE, UL, EAC, VDE-AR-N 4105/ 4110. CSA

Marine ………………………………….. LR (Type Approval), ABS (Type Approval)