CE In conformity with the applicable
requirements of the following Standards
EN 61000-6-2. 2005: Generic Standards –
Immunity for Industrial Environments
EN 61000-6-4. 2007: Generic Standards –
Emissions for Industrial Environments
EN 61010-1. 2010: Safety requirements for
electrical equipment for measurement, control,
and laboratory use – Part 1: General
Requirements
Housing
Connection ………………. plug terminals 2.5 mm²
Weight …………………………………. approx. 770 g
Environmental
Ambient temp. …….. -40 to 70 °C / -40 to 158 °F
(operation, when mounted in landscape
orientation)
Ambient temp. …….. -55 to 85 °C / -67 to 185 °F
(storage)
Ambient humidity ………. 93 %, non-condensing
Vibration
5.05 G, 1 mm amplitude, 69 Hz in 3 orthogonal
planes
Generator Excitation Types
Self / Shunt Excitation, Internal / Auxiliary
Winding Excitation, Permanent Magnet (PMG),Single or Three Phase