Specifications
Power supply 12/24 Vdc (8 to 40 Vdc)
Intrinsic consumption max. 22 W
Ambient temp. (operation) -40 to 70 °C / -40 to 158 °F
Ambient temp. (storage) -40 to 80 °C / -40 to 176 °F
Ambient humidity 95 %, non-condensing
Voltage (software configurable) (Y / ∆)
100Vac Rated (Vrated) 69 / 120 Vac
Max value (Vmax) 86 / 150 Vac
400 / 600 VAC Rated (Vrated) 400 / 690 VAC
Max. value (Vmax) 520 / 897 VAC
Rated surge Volt. (Vsurge) 6.0 kV
Accuracy Class 0.5
Measurable alternator windings
3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w
Setting range primary 50 to 650.000 Vac
Linear measuring range 1.25×Vrated
Measuring frequency 50/60 Hz (30 to 85 Hz)
High Impedance Input; Resistance per path 2.5 MΩ
Max. power consumption per path < 0.15 W
Current (Isolated, software configurable)
Rated (Irated) 1 A or 5 A
Linear measuring range IsystemA = 3.0×Irated
IsystemB = 1.5×Irated
Setting range 1 to 32.000 A
Burden < 0.10 VA
Rated short-time overcurrent (1 s) [1] 50×Irated,
[5] 10×Irated
Accuracy Class 0.5