On-board Driver
The valve driver and wiring terminal box are integral with the valve assembly,
eliminating interconnecting wiring, reducing package size requirements, and
lowering the installed cost. The on-board driver can be interfaced to the turbine
control via redundant 4–20 mA input and feedback signals, through redundant
CANopen control networks, or through redundant real-time Ethernet networks. The
GS-Series can be configured to accept both the 4–20 mA signal and CANopen/RT
Ethernet position command in a redundant configuration. With this arrangement, if
either demand signal fails, the driver will switch to the healthy input demand signal.
The valve driver operates with a 90-150 VDC or 18-32 VDC power supply,
depending on the model.