The MSLC-2 provides phase matching or slip frequency synchronization, with voltage matching,
across a utility or intertie breaker. The MSLC-2/DSLC-2 combination can handle multiple utility con
nections with a maximum of 8 bus segments in one application.
The MSLC-2’s load sensor and load control sense true RMS power and provide a bump-less load
ing and unloading against a utility grid. Baseload, import/export, process, and utility unload modes
control the KW power between different power sources at the same time controlling the reactive
power, VAR and power factor. Reactive power is also ramped on and off for the smoothest load
transactions between power grids.
The MSLC-2 communicates via Ethernet, with redundant Ethernet now available, to control real
and reactive loading against the utility by DSLC-2 equipped generators.
The tie breaker mode allows synchronization between multiple generator systems. Segments are
connected and power can be measured across an intertie, but no load control is functional when in
Tie breaker operation.