Discrete Inputs
The discrete inputs are the switch input commands to the MSLC. Discrete inputs
are optically isolated from the control and require 10 mA at 24 Vdc each to
activate. Discrete inputs may be powered by the same source as control power.
All contacts used in the discrete circuits should be the isolated dry contact type to
work properly with the low currents used in these circuits.
Connect the 24 Vdc supply common (–) to terminal 43. Route +24 Vdc through
the appropriate external contact to the discrete input.
Synchronizer Mode Switch
The synchronizer mode switch (single-pole, four-position) controls the operating
mode of the synchronizer. The switch must be wired to terminals 44. 45. and 46.
as shown in Figure 1-3. The four positions are Off, Check mode, Permissive
mode, and Run mode. When the switch is off, the synchronizer is out of operation.