Ramp Pause Contact
Connect the load ramp pause switch contact to terminal 51. When closed, this
contact will hold any load ramp in progress at its current setting until the contact is opened.
Raise and Lower Set Point Contacts
Connect a center off, double-pole double-throw switch to the Raise and Lower
Load inputs, terminals 52 and 53. If the remote reference will be used, install a
second double-pole double-throw switch to simultaneously select both the Raise and Lower inputs.
Local Bus Voltage Adjustment Contacts
The Local Bus voltage adjustment contact inputs allow manual voltage control of
the operating generator’s voltages for manual paralleling. Note, if the individual
generators are in VAR/PF control, they will return to VAR/PF control as soon as
the MSLC’s raise/lower switches are returned to OFF. The switches may also be
used to change the constant generator power factor reference if operating in that mode.