Valve Status (local & remote)
Each valve solenoid accepts power for one or two (redundant) power sources and has the following
status indications to assist operators with understanding the status and health of each valve.
• Valve Open—Local LED (red)
• Valve Open—Limit Switch
• Valve Closed—Local LED (green)
• Valve Closed—Limit Switch
• Power Supply #1 Healthy—Local LED (blue)
• Power Supply #2 Healthy—Local LED (blue)
Redundancy/Availability
Designed for use in critical gas and steam turbine applications where turbine up time is important, the
QuickTrip uses three isolated solenoid valves designed to be driven by a triple modular redundant 2-out
of-3 voting based safety logic solver. Each isolated solenoid valve uses redundant power supply inputs to
increase both system reliability and availability. Note: only one power source is required to
power/energize each of the isolated solenoid valves.
On-Line Repairable
The QuickTrip’s modular design allows independent repair/replacement of each valve’s solenoid,
electrical module, and associated power supplies and wiring to increase both system reliability and
availability. Note: only one power source is required to power/energize each of the isolated
solenoid valves.