SPECIFICATIONS (for more see specific manuals)

Accuracy………………………………………………………………………………Class 1

Power supply……………………………………………[Standard] 24 Vdc (+/-25 %)

[N & XN Packages] 90 to 250 Vac/dc

Intrinsic consumption…………………………………………………………max. 10 W

Ambient temperature……………………………………………………….-20 to 70 °C

[N & XN Packages] -20 to 60 °C

Ambient humidity………………………………………………95 %, non-condensing

Voltage………………..Rated /Δ: [1] 66/115 Vac or [4] 230/400 Vac

Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac

Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac

Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV

Measuring frequency………………………………………………………..40 to 70 Hz

Linear measuring range up to……………………………………………….1.3×Vrated

Input resistance………………………………………….[1] 0.21 MΩ, [4] 0.696 MΩ

Max. power consumption per path…………………………………………< 0.15 W

Discrete inputs…………………………………………………………………… isolated

Input range…………………………………………………………..max. 250 Vac or dc

Input resistance……………………………………………………………approx. 68 kΩ

Relay outputs…………………………………………………………………….. isolated

Contact material…………………………………………………………………….AgCdO

Load (GP)…………………………………………………………….2.00 Aac@250 Vac

2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc

Pilot duty (PD)………………………………………………………………………………….

1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc

Housing………………………………………………Type APRANORM DIN 43 700

Dimensions……………………………………………………………..144×72×122 mm

Front cutout……………………………………………………138[+1.0]×67[+0.7] mm

Connection…………………………………………screw/plug terminals depending

on connector 1.5 mm² or 2.5 mm²

Front………………………………………………………………………insulating surface

Protection system…………………………………………..with correct installation

Front………………………………………….IP42

(sealed IP54; gasket kit = P/N 8923-1037)

Back………………………………………….IP21

Weight…………………………………………………………………………approx. 800 g

Disturbance test (CE)……….tested according to applicable EN guidelines

Listings…………………………………..UL/cUL listed (voltages up to 300 Vac)