SPECIFICATIONS (for more see specific manuals)
Accuracy………………………………………………………………………………Class 1
Power supply……………………………………………[Standard] 24 Vdc (+/-25 %)
[N & XN Packages] 90 to 250 Vac/dc
Intrinsic consumption…………………………………………………………max. 10 W
Ambient temperature……………………………………………………….-20 to 70 °C
[N & XN Packages] -20 to 60 °C
Ambient humidity………………………………………………95 %, non-condensing
Voltage………………..Rated /Δ: [1] 66/115 Vac or [4] 230/400 Vac
Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac
Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac
Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV
Measuring frequency………………………………………………………..40 to 70 Hz
Linear measuring range up to……………………………………………….1.3×Vrated
Input resistance………………………………………….[1] 0.21 MΩ, [4] 0.696 MΩ
Max. power consumption per path…………………………………………< 0.15 W
Discrete inputs…………………………………………………………………… isolated
Input range…………………………………………………………..max. 250 Vac or dc
Input resistance……………………………………………………………approx. 68 kΩ
Relay outputs…………………………………………………………………….. isolated
Contact material…………………………………………………………………….AgCdO
Load (GP)…………………………………………………………….2.00 Aac@250 Vac
2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Pilot duty (PD)………………………………………………………………………………….
1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Housing………………………………………………Type APRANORM DIN 43 700
Dimensions……………………………………………………………..144×72×122 mm
Front cutout……………………………………………………138[+1.0]×67[+0.7] mm
Connection…………………………………………screw/plug terminals depending
on connector 1.5 mm² or 2.5 mm²
Front………………………………………………………………………insulating surface
Protection system…………………………………………..with correct installation
Front………………………………………….IP42
(sealed IP54; gasket kit = P/N 8923-1037)
Back………………………………………….IP21
Weight…………………………………………………………………………approx. 800 g
Disturbance test (CE)……….tested according to applicable EN guidelines
Listings…………………………………..UL/cUL listed (voltages up to 300 Vac)