DESCRIPTION
Protection ANSI #
• Single-phase CT sensing for generator
• Two-phase sensing of generator voltage
• Generator over-/undervoltage (59/27)
• Generator over-/underfrequency (81O/U)
• Generator reverse/reduced power (32R/F)
• Generator overload (32)
Control outputs
LSXR Package
• Analog bias outputs for voltage and speed
freely configurable for all levels (+/-1 V, +/
3 V, 0 to 5 V, 0.5 to 4.5 V, +/-10 V +/-5 V, 0
to 20 mA, +/-20 mA, and much more
configurable)
• Speed bias output configurable as 500 Hz
PWM output and adjustable voltage level
• Two raise/lower outputs configurable for
either speed or voltage
Operating Features
• Two-line Liquid Crystal display for operation
and alarm indication
• Synchroscope
• Indication of control activity and breaker state
• Multi-level password protection for parameters
• Configuration directly or via PC
• English or German language adjustable