SPECIFICATIONS (for more see specific manuals)

Accuracy ……………………………………………………………………………… Class 1

Power supply 12/24 Vdc (9.5 to 32 Vdc)

Intrinsic consumption ………………………………………………………… max. 10 W

Ambient temperature………………………………………………………. -20 to 70 °C

Ambient humidity……………………………………………… 95 %, non-condensing

Voltage …………………Rated /∆: [1] 66/115 Vac or [4] 230/400 Vac

Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac

Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac

Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV

Measuring frequency……………………………………………………….. 40 to 70 Hz

Linear measuring range up to ………………………………………………. 1.3×Vrated

Input resistance …………………………………………. [1] 0.21 MΩ, [4] 0.696 MΩ

Max. power consumption per path ………………………………………… < 0.15 W

Current (Irated) ……………………………………………………….. [1] ../1 A, [5] ../5 A

Linear measuring range up to ……………………………………………….. 3.0×Irated

Load ………………………………………………………………………………… < 0.15 VA

Rated short-time current (1 s) ……………………………[1] 50×Irated, [5] 10×Irated

Discrete inputs …………………………………………………………………… isolated

Input range …………………………………………… 12/24Vdc or 18 to 250 Vac/dc

Input resistance ……………………………………………. approx. 6.8 kΩ or 68 kΩ

Relay outputs …………………………………………………………………….. isolated

Contact material ……………………………………………………………………. AgCdO

Load (GP) ……………………………………………………………. 2.00 Aac@250 Vac

2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc

Pilot duty (PD) ………………………………………………………………………………….

1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc

Housing ……………………………………………… Type APRANORM DIN 43 700

Dimensions ……………………………………………………………..144×72×122 mm

Front cutout …………………………………………………… 138[+1.0]×67[+0.7] mm

Connection ………………………………………… screw/plug terminals depending

on connector 1.5 mm² or 2.5 mm²

Front ……………………………………………………………………… insulating surface

Protection system ………………………………………….. with correct installation

Front …………………………………………. IP42

(sealed IP54; gasket kit = P/N 8923-1037)

Back …………………………………………. IP21

Weight ……………………………………….. depending on version, approx. 800 g

CE approval ……………………. tested according to applicable EN guidelines

Listings ………………………………….. UL/cUL listed (voltages up to 300 Vac)