OPERATION
The BE3-47N and BE3-47N/27 phase balance relays have
two external, user-adjustable controls marked UNBAL and
DELAY. The UNBAL control adjusts the relay trip point. The
relay trips when the voltage becomes unbalanced by the
percentage set by the UNBAL control. The trip point is
adjustable from 5 to 15% (±5%) of nominal input. The
DELAY control adjusts the time from when a fault is
detected until the output contacts change state. The delay is
adjustable from 0 to 10 seconds. The undervoltage feature
of the BE3-47N/27 has no external adjustment and is fixed
at 85% of the nominal input voltage. If all three phases
remain balanced, but decrease below 85% of nominal
voltage, the relay de-energizes.