Functional Description
Introduction
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Measuring Values
• Voltage
Three-phase measurement of the rms values of the phase-to-neutral and
phase-to-phase voltages of two systems (system [A] and [B]; system [B]
only phase-to-phase). This unit can be delivered with the following measuring
voltage ranges (rated values). Selection of type during ordering:
– 66/115 Vac – 230/400 Vac
• Frequency
Time measurement from the digitally filtered measuring voltages. The
measurement of the frequency is three phased if all voltages are greater
than 15 % of the rated value (100 Vac or 400 Vac). This guarantees a fast
and precise measurement of the frequency. However the frequency is still
measured correctly even if voltage is only applied to one phase.
• Current
Three-phase rms values.
• Real power
Single-phase measuring calculated from apparent power and power factor
cosphi (power factor).
• Re-active power
Single-phase measurement calculated from apparent power and power factor
sinphi.
• Power factor cosphi
Time measurement between the filtered measuring values of the voltage VL12
and the conductor current IL1.