Dead Bus Start
A close CB command without synchronization may be issued if the following
conditions are fulfilled simulta neously:
• Dead bus start function is configured to ON (Parameter 43).
• Discrete input “Enable CB” is set.
• Discrete input “Reply: CB is open” is set.
• One of the three possible black start functions is enabled
1.) Parameter 46 (Vsystem A=Vn/Vsystem B=0)
Vsystem A is equal with Vn (using the configured rated voltage difference dV
|V-Vn|) and Vsystem B is zero (using the configured zero voltage difference
dV |V-0|).
2.) Parameter 45 (Vsystem A=0/Vsystem B=Vn)
Vsystem A is zero (using the configured zero voltage difference Vd |V-0|) and
Vsystem B is equal with Vn (us
ing the configured rated voltage difference dV |V-Vn|).
3.) Parameter 44 (Vsystem A=0/Vsystem B=0)
VA is zero and VB is zero (using the configured zero voltage difference dV |V-0|).
• No alarm is triggered if parameter “Blocking at dead start alarm” is configured
to ON (Parameter 51).
• No GCP is trying to carry out a dead bus start.
• No higher prioritized LS 4 is trying to close its breaker.