M‑3410A Intertie/Generator Protection Relay – Specification
The M-3410A Intertie/Generator Protection Relay is intended for the
protection of the intertie between the utility and dispersed generation.
It is also suitable for the protection of synchronous and induction
generators.
Communications and control features of the M-3410A are accomplished
utilizing the M-3810A IPScom for Windows Communications Software.
Oscillographic Recorder
The oscillographic recorder provides comprehensive data recording of all
monitored waveforms, input contacts, and output contacts, storing up to
120 cycles of data. The total record length is configured for one or two
partitions. A programmable post trigger delay (5 to 95%) is incorporated
to capture breaker operation.
The oscillograph is triggered remotely using the serial interface, designated
status input signals, or M-3410A programmable output operations.
Storage of oscillographic records is nonvolatile and will be retained even
without power, as long as the on-board battery is healthy.
Oscillographic data can be downloaded using serial communication in
Common Format For Transient Data Exchange (COMTRADE) format as
specified by IEEE Standard C37.111-1999.