Description

M‑3410A Intertie/Generator Protection Relay – Specification

The M-3410A Intertie/Generator Protection Relay is intended for the

protection of the intertie between the utility and dispersed generation.

It is also suitable for the protection of synchronous and induction

generators.

Communications and control features of the M-3410A are accomplished

utilizing the M-3810A IPScom for Windows Communications Software.

Oscillographic Recorder

The oscillographic recorder provides comprehensive data recording of all

monitored waveforms, input contacts, and output contacts, storing up to

120 cycles of data. The total record length is configured for one or two

partitions. A programmable post trigger delay (5 to 95%) is incorporated

to capture breaker operation.

The oscillograph is triggered remotely using the serial interface, designated

status input signals, or M-3410A programmable output operations.

Storage of oscillographic records is nonvolatile and will be retained even

without power, as long as the on-board battery is healthy.

Oscillographic data can be downloaded using serial communication in

Common Format For Transient Data Exchange (COMTRADE) format as

specified by IEEE Standard C37.111-1999.