Cross-section: Gas inlet CEMTEC probe tube
The CEMTEC is self-cleaning, which enables continuous measurement and
thus 95% availability during the process. In addition to the in-situ sensors
for oxygen and COe analysis, the extractive analyzers are supplied with
dust-free sample gas for the determination of, for example, SO₂, NOₓ, or
CO₂. Thanks to mechanical cleaning, the uninterrupted extraction and
analysis of process gas is possible over extended periods: The filter/seal at
the gas inlet continuously breaks down deposits and blockages, ensuring
an uninterrupted gas supply. The patented swivel drive rotates the probe
at programmable intervals, thus preventing material from accumulating on
the probe tube. Together with the powerful pneumatic drive motor, the
probe can perform a controlled retraction at any time.
Technical data
Process gas temperature ≤ 1400 °C
Immersion depth/material up to 4.5 m
Dust loading up to 2000 g/m³
Probe cooling method Air/coolant or water/coolant
Probe operation 100% pneumatic drives (extension and retraction, rotation,
plunger and flushing)
Leave a comment
Your email address will not be published. Required fields are marked *