Woodward DTSC-200A Automatic Transfer Switch (ATS) Controller FEATURES In-phase
• Inhibit transfer to S1. S2. both or start emergency source but initiate no transfer
• Elevator pre-signal with timer before carrying out a transfer
• Motor load disconnect signal with timer and possibility to daisy chain multiple MLDs for load
sequencing
• Source priority selection configurable via LogicsManager
• Load test and engine test to initiate routine health check of the emergency source
• In-phase monitoring ensures a transfer occurs within a phase angle difference of 70 or less
• Extended parallel time enables soft loading applications
• Vector group adjustment if transformers are used in the ATS system
• Shunt trip enable signal ensures both sources are not paralleled for more than desired time
• Remote control via interface (CANopen, Modbus RTU) and via discrete inputs
• I/O expansion capability (additional 16x DI and 16x DO supported via IKD1M or 3rd party modules)
• Adjustable display backlight shutdown to reduce power consumption
• Woodward ToolKit™ software for flexible setup from a single connection to the network. Supports
settings file created from the DTSC-200
• Multi-lingual capability: English, German, Spanish, Polish, Russian, other languages upon request