Welcome to the official website of CNIACS Automation Technology Co., Ltd!

CTI 2541 Redundant Processor Manager Module

The 2541 Redundant Processor Manager (RPM) provides an automatic

backup solution for 2500 Series® PLCs. If the active PLC fails, the RPM

will automatically switch the remote I/O to the standby PLC.

Transfer to the standby PLC is bumpless. All remote I/O updates are

mirrored to the standby PLC. In addition, up to 4096 words of user-

defined critical data can be transferred from the active PLC to the 

standby PLC every scan.

Other non-critical data can be transferred over several scans.

The RPM can also switch up to two serially attached operator interface

devices.

IMPORTANT NOTE: Due to extensive component obsolescence issues

and insufficient demand to justify a re-engineering effort, this product

has been matured.  For users needing PLC redundancy in the future,

we have a solution planned based on our new Janus Programmable

Automation Controller which uses two Janus PLCs and a Modbus relay

that switches Remote I/O and Profibus networks from the primary PLC

to the backup in case of a Processor failure.

CTI 2577 Profibus DP Slave Adapter

The 2577 allows a Profibus Master to read any PLC V, WX, X, and C

memory location and write any V, WY, and C memory location over

Profibus.

Features

• No changes required to existing PLC configuration and I/O

• Allows transfer of up to 110 words of data in and 110 words of data

out to Profibus Master

• Maintains statistics and diagnostic information for the Profibus network

• Auto-senses Profibus baud rate

• Integrates CTI 2500 Series® and Simatic® 505 systems into S7 and

PCS7 designs

Files & Documents

• VUser Manual

• Quick Start Guide

• Product Bulletin

• GSD File

Application Notes

• Configuring the 2577 Profibus-DP Slave Adapter using Workshop

Technical Advisories

• Using 2577 Profibus Slave Adapter with 2500 Series® Processors

(March 6.2008)

• Configuring the CTI 2577 Profibus Adapter with some versions of COM Profibus and Step 7

CTI 2573-MOD Serial Interface Adapter with MODBUS

The 2573-MOD provides support for communicating with serial and Modbus

plant floor devices such as modems, bar code readers, scales, displays,

printers, and other PLCs.

Features

• Provides 4 serial ports, each providing RS-422. RS-485 and RS-232 electrical

interfaces. All ports operate concurrently and independently.

• Enables the PLC to act as a master or slave for devices which use Modbus

RTU or ASCII protocols

• Task Code Master support allows the local PLC to access memory in other

2500 Series® or Simatic® 505 PLCs

Application Notes

• 2573-TCM2 to Mettler/Toledo PG5001 Scale

• Upgrading from a Siemens® Simatic® 505-5184 Module

• 2573-TCM2 to Ohaus IP Series High Capacity Precision Toploaders

• 2573-TCM2 to Mettler/Toledo SM3000 Scale

• 2573-MOD to 3300 ACM Digital Power Meter

• 2573-TCM2 to MTS Digital Access Tank Gauge

• 2573-MOD to S7-200 PLC

• Distributed PID Temperature Control From a PLC using Eurotherm Series

2000 PID Temperature Controllers with Modbus RTU Communications

• Using the CTI 2573-MOD Serial Interface Adapter with Microwave Data

Systems Master/Remote Radios

CTI 2572-AF Fast Ethernet TCP/IP Adapter with Optical Fiber Connection

The 2572-AF Ethernet TCP/IP Adapter with Optical Fiber

Connection is the next generation 2572 network interface

module for 2500 Series® controllers.

The 2572-A provides connectivity to Ethernet networks

using IEEE 802.3. Ethernet II and Transmission Control/

Internet Protocol standards, at 10M or 100M speeds.

IMPORTANT NOTE: 2572-AF HAS BEEN MATURED. 

IT IS REPLACED BY 2572-B or 2500P-ECC1.

WHICH SHOULD BE USED ON ALL NEW DESIGNS.

Features

• Compatible with Siemens® 505-CP2572 and CTI 2572

• Direct Fiber MTRJ connection

• TCP/IP support includes UDP and TCP

• Remote programming over Ethernet

• MMI/HMI connectivity

• DDE and OPC support available

• DHCP configuration option

• Built-in web server for diagnostics

CTI 2572-A Fast Ethernet TCP/IP Adapter

The 2572-A Ethernet TCP/IP Adapter is the next generation

2572 network interface module for 2500 Series® or Simatic®

505 controllers. The 2572-A provides connectivity to Ethernet

networks using IEEE 802.3. Ethernet II and Transmission

Control/Internet Protocol standards, at 10M or 100M speeds.

IMPORTANT NOTE: 2572-A HAS BEEN MATURED.

IT IS REPLACED BY 2572-B or 2500P-ECC1.

WHICH SHOULD BE USED ON ALL NEW DESIGNS.

Features

• Compatible with Siemens® 505-CP2572 and CTI 2572

• Auto-sensing for 10/100Mbps networks

• TCP/IP support includes UDP and TCP

• Supports Modbus-TCP and Ethernet/IP protocols

• Remote programming over Ethernet

• MMI/HMI connectivity

• DDE and OPC support available

• DHCP configuration option

• Built-in web server for diagnostics

CTI 2572-A Application Notes

Application Notes

• Guide for Converting Ethernet Applications from 2572 /

2572-A / 2572-B to 2500P-ECC1

• Setting the IP address using the PLC on 2572-A and

2572-B (Tech Tip)

• 2572 Installation and Setup Instructions

• Assigning an IP Address to the 2572-A without Connecting

to the Module

• Communication to Simatic S7 Using Open Modbus

• Creating a Client/Server Memory Transfer between Two

2572-X Modules

• Getting Started with Networking and the 2572

• Reading Values into Excel Spreadsheets Using the 2572

• Replacing a Peerlink Network with Ethernet and 2572-A

• Using CTIDIAG with the 2572

• Using the 2572 UDP “Send To” Feature to Exchange Memory

with Multiple PLCs

• Using the 2572 with Wonderware 7.0

• IP Addressing and the 2572

• Starting the 2572 Network Server from PLC Logic

CTI 2572-B Fast Ethernet TCP/IP Adapter

The 2572-B Fast Ethernet TCP/IP Adapter is the next generation Ethernet

network interface module for 2500 Series® or Simatic® 505 controllers.

The 2572-B provides connectivity to Ethernet networks using IEEE 802.3.

Ethernet II and Transmission Control/Internet Protocol standards, at 10M

or 100M speeds.

For help selecting the right Ethernet solution for your needs, see our

Tech Tip:

Ethernet Communications: What is the Best Solution for Your Needs?

or click on the link below to get help from an Applications Engineer.

Get Help With Ethernet

Features

• Direct replacement for 2572-A

• Compatible with CTI 2572-A, CTI 2572. and Siemens® 505-CP2572

• New IP address display on front panel

• No serial connection required to set IP address

• DHCP address switches eliminated (contact CTI if your application

uses DHCP)

• Auto-sensing for 10/100Mbps networks

• TCP/IP support includes UDP and TCP

• Supports Modbus-TCP and Ethernet/IP protocols

• Remote programming over Ethernet

• MMI/HMI connectivity

• DDE and OPC support available

• Built-in web server for diagnostics

CTI 2500S-27-1050 Features

Features

• I/O configuration of 2DIO / 4UAI / 2AI

• RJ45 Ethernet port

• Connects to CTI and legacy Siemens® /TI CPUs over Ethernet

• Several models with differing I/O capabilities allow you to customize

the solution to your needs

• Extensive intelligent features for processing attached I/O signals:

– Totalization, filtering, forcing, inversion, runtime, and counting on

digital inputs

– Frequency out (with PWM) and synchronization on digital outputs

– Filtering, averaging, scaling and totalization on analog inputs

– Data logging and trending

• All module configuration done using a simple web browser interface

• Wide –40°C to +70°C operating temperature range

CTI 2500S-27-1050 Slice I/O, Ethernet, 2DIO / 4UAI / 2AI (MATURE)

The 2500S family of Slice I/O modules expands the capability of 2500

Series® Systems to include small drops of I/O connected over Ethernet.

Slice I/O modules communicate to 2500 Series® Processors using CAMP

protocol and read/write directly to the PLC memory or I/O image table.

This allows transparent integration into the 2500 Series® system without

the requirement for any complicated configuration step.

Ethernet connection to the CPU can be accomplished using the on-board

port on 2500-Cxxx Processors, or using a 2572 / 2572-A Ethernet module.

Note that when using 2572 or 2572-A modules, Slice I/O can be connected

even to legacy Siemens® and Texas Instruments PLCs.

Several models of Slice I/O are available with different mixes of I/O and with

additional communications options including RS232/485 and 900MHz radio.

Slice I/O modules feature Universal Analog Inputs which allow connection

of 0-5V, 0-20mA, thermocouple, and RTD sensors. All Slice I/O modules can

also be configured to communicate over Ethernet using Modbus-TCP.

Note: This unit is designed to work on a battery so +12VDC is operating

voltage, not +24VDC.

NOTE: THIS PRODUCT IS MATURE AND IS  NO LONGER AVAILABLE FOR

PURCHASE.

CTI 2500S-26-1050 Features

Features

• I/O configuration of 8DIO / 2UAI

• RJ45 Ethernet port

• Connects to CTI and legacy Siemens® /TI CPUs over Ethernet

• Several models with differing I/O capabilities allow you to customize

the solution to your needs

• Extensive intelligent features for processing attached I/O signals:

– Totalization, filtering, forcing, inversion, runtime, and counting on digital inputs

– Frequency out (with PWM) and synchronization on digital outputs

– Filtering, averaging, scaling and totalization on analog inputs

– Data logging and trending

• All module configuration done using a simple web browser interface

• Wide –40°C to +70°C operating temperature range

Search for products