Overexcitation Time Delay
If the regulator output voltage exceeds 65 Vdc ±2 Vdc, the
regulator automatically makes a connection across
terminals A1 and A2 via an optically-isolated triac device.
This occurs after a time delay which is inversely
proportional to the magnitude of the regulator output
overvoltage condition up to approximately 105 Vdc ±5 Vdc
(see Figure 2). Beyond this point, the field voltage is
removed at a much faster rate. To avoid tripping due to
the voltage provided by a separate current boost circuit,
voltage measurement excludes any additional boost
voltage term. The overexcitation circuit is reset by
reducing the regulator input voltage to less than its buildup
value for 5 seconds.
This feature is designed to protect the generator and
regulator by allowing disconnection of the overloaded
part(s) of the system. Should the regulator be allowed to
run in excess of its rated current for any extended period
of time after the protection output closes, failure of the
recommended supply fuse will occur, but regulator
damage may also take place.