Trip Timing
Within the relay are two timers that control operation of the device. Timer 1 defines the delay time between
recognition of the breaker trip signal and the interrogation of the current monitoring circuits for the presence
of current. Adjustment range for this timer is 18 to 500 milliseconds.
At the same time that timer 1 is initiated, the control timer is also initiated. Figure 1-1 illustrates the trip
timing relationships. The purpose of the control timer is to increase security by limiting the response time
of the relay to a short period following any given attempt to interrupt the breaker. The control timer also
terminates the closure of the BF output relays, and breaks the seal of the seal-in circuit (if used).
Breaker failure initiate (BFI) input seal-in is selected by closing printed circuit board switch S1-3 (refer to
Section 2 for location and Section 3 for logic block diagram). This selection may be required when current
from an isolated weak source cannot be depended on to maintain the minimum signal level to the protective
relays initiating the BFI input. Such a condition can occur when the fault voltage is depressed to zero. The
seal-in feature may also counteract contact bounce.
An optional supervisory contact input to the BE1-50BF relay may be specified. When the supervisory
contact input is specified, a third timer (timer 2) is built into the relay. Timer 2 (plus associated circuitry
together with the supervisory contact) duplicates the corresponding features of the timer 1 system. This
addition allows different breaker failure times for different types of failures.
As an example, it might be desirable to use a shorter tripping time if the breaker mechanism fails to operate
(all three breaker poles failed to clear the fault). If the mechanism did operate, but only one of the poles
failed to clear, a longer breaker failure time might be appropriate. This protection can be provided by
connecting the BFI input in series with a 52a contact of the breaker to the supervisory contact input and
setting the delay on timer 2 shorter than timer 1. If the breaker mechanism failed to operate, the breaker
failure relay would be controlled by timer 2. If the breaker mechanism did operate, timer 2 would (in time)
reset and the breaker failure relay would be controlled by timer 1.
This scheme (BFI in series with 52A to supervisory input) allows for 52A or current supervision of the BF
timers 1 and 2. If 52A supervision is desired, switch S1-7 would be closed. Refer to Section 3 block diagram
for logic details.