Percentage Restraint
A primary concern in differential relay applications is security against high current levels caused by faults
outside the protected zone. Inevitable differences in the saturation characteristics between current
transformers require a compensating decrease in relay sensitivity. It is also necessary to be able to adjust
the sensitivity to compensate for transformer voltage taps or CT mismatches. This is accomplished by
providing a restraint factor proportional to the current flowing through the protected zone (through
current).
BE1-87T relays maintain sensitivity at a specified ratio of trip current to through current. This ratio,
generally referred to as slope, is front-panel adjustable in 5 % increments from 15 to 60 %.
Fifth-Harmonic Restraint
Power transformer overexcitation causes additional exciting current to flow into one set of terminals. This
presents an apparent differential (or operating) current not attributable to an internal fault. Although
potentially damaging, overexcitation is not an internal fault and, therefore, is not an appropriate condition
for transformer differential relay operation. One of the principal components in the complex waveform
produced during overexcitation is the fifth harmonic. BE1-87T relays use fifth-harmonic restraint to inhibit
the differential relay operation.